Copyrigh©Qingdao Jinyudun Energy Equipment Co., Ltd.

Diesel Generator Sets

Our Generator Set ranges

Shangchai 50KW generator set

Shangchai 50KW generator set

Categories:

Diesel generator set

Brand:

Shangchai series

Configuration:

Open-frame unit

Diesel generator set parameters:

National II series:

Diesel generator set parameters:

model

FFDL-S50GF

Unit power (KW)

50

Output voltage (V)

400/230

Rated output current (A)

90

Wiring method

Three-phase four-wire

Power factor

0.8 (Lag)

Startup method

24V DC start

Frequency (Hz)

50

Unit weight (kg)

800

Unit dimensions (reference values)

1800*730*1300mm

Altitude (m)

1500

steady-state voltage regulation

≤±2.5%

steady-state frequency regulation

≤±5%

steady-state voltage fluctuation

≤±1%

Steady-state frequency volatility

≤±0.5%

Transient voltage regulation

-15% to +20%

Transient frequency regulation

-10% to +10%

Voltage settling time

≤1S

 

Diesel engine parameters

Diesel engine brands

Serve firewood

model

SC4H95D2

Rated speed (pm)

1500

Power (kW)

62/68

Number of cylinders

4-cylinder

Cylinder arrangement

inline

Cylinder bore * stroke (mm)

105*124

Compression ratio

17.3:1

Speed adjustment method

Electronic speed control

fuel supply method

direct injection

fuel

China 0# light diesel oil

Minimum fuel consumption rate (g/kw.h)

195

intake method

Boost

Oil consumption rate (g/kw.h)

≤0.3

steady-state rate of adjustment

≤5%

Emission standards

Country II

Cooling method

Water tank radiator that meets ambient temperature requirements up to 40℃, belt-driven cooling fan, with fan safety cover.

 

Generator parameters

Generator brand: Stamford

Manufacturer: Cummins Generator Technology (China) Co., Ltd.

Generator model: UCI224E1/S1L2-Y1

Capacity: 60KVA

Voltage: 400V/230V

Types: Brushless, single bearing, rotating magnetic field

Excitation system: self-excited, automatically regulating voltage

Winding structure: 2/3 pitch

Number of phases: Three-phase four-wire

Insulation class: Class H

Power factor: COSΦ = 0.8 lag

Telephone interference factor: TIF: <50

Wiring: Y-type connection

Telephone harmonic distortion (THF): <2%

Protection rating: IP23

Radio interference: Meets BS800 and VDE G and N levels

Meets the following standards: GB755, BS5000 Part 3, VDE0530, NEMA MG1-22, IEC-34, GSA C22-100, AS1359

Calibration Environment
: • Ambient Temperature: ≤40℃ • Relative Humidity: ≤60% • Altitude: ≤1000m
• Complies with ISO3046 and ISO8528 requirements.
Optional Configurations
: • Automatic Load Transfer Switch (ATS) • Automatic Parallelization Switch (DSE) (Deep-sea DSE Control Module)
• Containerized Generator Set
• Mobile Trailer-Mounted Power Station
• Rainproof Generator Set
• Silent Mobile Power Station
• Remote Microcomputer Interface
• Spare Parts with 500-1000 Hours of Operation


We blend China’s manufacturing strength with quality/service