Categories: |
Diesel generator set |
|
Brand: |
Weichai series |
|
Configuration: |
Open-frame unit |
National II series:
Diesel generator set parameters: | ||
Model : FFDL-W1000GF Output voltage (V) : 400/230 Wiring method : Three-phase four-wire Starting method : 24V DC power start Unit weight (kg) : 9500 Altitude (m) : 1500 Steady-state frequency regulation : ≤±5% Steady-state frequency fluctuation : ≤±0.5% Transient frequency adjustment rate : -10% to +10% | Unit power (KW) : 1000 Rated output current (A) : 1800 Power factor : 0.8 (lagging) Frequency (Hz) : 50 Unit dimensions (reference values) : 4800*2050*2450mm Steady-state voltage regulation : ≤±2.5% Steady-state voltage fluctuation rate : ≤±1% Transient voltage regulation : -15% to +20% Voltage settling time : ≤1s | |
Diesel engine parameters | ||
Diesel engine brand : Weichai Power Baudouin Rated speed (rpm) : 1500 Number of cylinders : 12 Cylinder bore * stroke (mm) : 150 * 185 Speed control method : Electronic speed control Fuel : China 0# light diesel oil Intake method : turbocharged intercooler Steady-state rate of adjustment : ≤5% | Model : 12M33D1210E200 Power (kW) : 1100/1210 Cylinder arrangement : V-type Displacement : 39.2 Fuel supply method : direct injection Minimum fuel consumption rate (g/kw.h) : 210 Oil consumption rate (g/kw.h) : ≤0.3 Emission standard : China II | |
Cooling method Water tank radiator that meets ambient temperature requirements up to 40℃, belt-driven cooling fan, with fan safety cover. | ||
Generator parameters | ||
Generator brand: Stamford Manufacturer: Cummins Generator Technology (China) Co., Ltd. Generator Model: S6L1D-F4/HCI634K/LVI634F Rated capacity: 1150KVA/1135KVA/1130KVA Voltage: 400V/230V Types: Brushless, single bearing, rotating magnetic field Excitation system: self-excited, automatically regulating voltage Winding structure: 2/3 pitch Number of phases: Three-phase four-wire | Insulation class: Class H Power factor: COSΦ = 0.8 lag Telephone interference factor: TIF: <50 Wiring: Y-type connection Telephone harmonic distortion (THF): <2% Protection rating: IP23 Radio interference: Meets BS800 and VDE G and N levels Meets the following standards: GB755, BS5000 Part 3, VDE0530, NEMA MG1-22, IEC-34, GSA C22-100, AS1359 | |
National III series:
Diesel generator set parameters: | ||
Model : FFDL-W1000GF Output voltage (V) : 400/230 Wiring method : Three-phase four-wire Starting method : 24V DC power start Unit weight (kg) : 9500 Altitude (m) : 1500 Steady-state frequency regulation : ≤±5% Steady-state frequency fluctuation : ≤±0.5% Transient frequency adjustment rate : -10% to +10% | Unit power (KW) : 1000 Rated output current (A) : 1800 Power factor : 0.8 (lagging) Frequency (Hz) : 50 Unit dimensions (reference values) : 4800*2050*2450mm Steady-state voltage regulation : ≤±2.5% Steady-state voltage fluctuation rate : ≤±1% Transient voltage regulation : -15% to +20% Voltage settling time : ≤1s | |
Diesel engine parameters | ||
Diesel engine brand : Weichai Power Baudouin Rated speed (rpm) : 1500 Number of cylinders : 12 Cylinder bore * stroke (mm) : 150 * 185 Speed control method : Electronic speed control Fuel : China 0# light diesel oil Intake method : turbocharged intercooler Steady-state rate of adjustment : ≤5% | Model : 12M33D1240E310 Power (kW) : 1100/1210 Cylinder arrangement : V-type Displacement : 39.2 Fuel supply method : direct injection Minimum fuel consumption rate (g/kw.h) : 210 Oil consumption rate (g/kw.h) : ≤0.3 Emission standard : China III | |
Cooling method Water tank radiator that meets ambient temperature requirements up to 40℃, belt-driven cooling fan, with fan safety cover. | ||
Generator parameters | ||
Generator brand: Stamford Manufacturer: Cummins Generator Technology (China) Co., Ltd. Generator Model: S6L1D-F4/HCI634K/LVI634F Rated capacity: 1150KVA/1135KVA/1130KVA Voltage: 400V/230V Types: Brushless, single bearing, rotating magnetic field Excitation system: self-excited, automatically regulating voltage Winding structure: 2/3 pitch Number of phases: Three-phase four-wire | Insulation class: Class H Power factor: COSΦ = 0.8 lag Telephone interference factor: TIF: <50 Wiring: Y-type connection Telephone harmonic distortion (THF): <2% Protection rating: IP23 Radio interference: Meets BS800 and VDE G and N levels Meets the following standards: GB755, BS5000 Part 3, VDE0530, NEMA MG1-22, IEC-34, GSA C22-100, AS1359 | |
Calibration Environment
: • Ambient Temperature: ≤40℃ • Relative Humidity: ≤60% • Altitude: ≤1000m
• Complies with ISO3046 and ISO8528 requirements.
Optional Configurations
: • Automatic Load Transfer Switch (ATS) • Automatic Parallelization Switch (DSE) (Deep-sea DSE Control Module)
• Containerized Generator Set
• Mobile Trailer-Mounted Power Station
• Rainproof Generator Set
• Silent Mobile Power Station
• Remote Microcomputer Interface
• Spare Parts with 500-1000 Hours of Operation
No. 120, West Liaoyang Road, Liaoyuan Road Subdistrict, Shibei District, Qingdao City, Shandong Province, China