Categories: |
Diesel generator set |
|
Brand: |
Volvo series |
|
Configuration: |
Open-frame unit |
Diesel generator set parameters: | ||||
Unit Model | LZ-V400 | Unit weight | 3230KG | |
Output power | 400KW/500KVA | Unit size | 3200*1200*1800mm | |
Power factor | COSΦ = 0.8 (hysteresis) | Voltage | 400/230 | |
Larger output current | 724A | frequency | 50Hz | |
Diesel engine parameters | ||||
Engine manufacturers | Volvo Sweden | Displacement | 16.12L | |
Engine Model | TAD1641GE | Engine structure | Inline 6-cylinder, four-stroke, turbocharged and intercooled | |
Rotation speed | 1500RPM | Engine cooling method | Closed-loop water cooling | |
power | 404/445KW | Speed control system | Electronic fuel injection | |
Fuel consumption | ≤200g/kw.h | Startup method | 24V DC start | |
Lubricating oil capacity | 64L | Engine Filtration System | Dry air filter, fuel filter, oil filter | |
cylinder bore × stroke | 144/165mm | |||
Compression ratio | 16.5:1 | |||
Generator parameters | |
Generator brand: Stamford Manufacturer: Cummins Generator Technology (China) Co., Ltd. Generator Model: S5L1D-C41/S5L1S-C41/HCI544C1 Capacity: 450KVA Voltage: 400V/230V Types: Brushless, single bearing, rotating magnetic field Excitation system: self-excited, automatically regulating voltage Winding structure: 2/3 pitch Number of phases: Three-phase four-wire | Insulation class: Class H Power factor: COSΦ = 0.8 lag Telephone interference factor: TIF: <50 Wiring: Y-type connection Telephone harmonic distortion (THF): <2% Protection rating: IP23 Radio interference: Meets BS800 and VDE G and N levels Meets the following standards: GB755, BS5000 Part 3, VDE0530, NEMA MG1-22, IEC-34, GSA C22-100, AS1359 |
Calibration Environment | |
No. 120, West Liaoyang Road, Liaoyuan Road Subdistrict, Shibei District, Qingdao City, Shandong Province, China