Categories: |
Diesel generator set |
|
Brand: |
Yuchai series |
|
Configuration: |
Open-frame unit |
Technical Specifications for 16kW Yuchai Diesel Generator Set
I. Technical Specifications
(1) Generator Set Model: GF-16
Prime Power (kW): 16
Standby Power (kW): 20.4
Frequency: 50Hz
Output Voltage: 400/230V
Speed: 1500 rpm
Power Factor: cosφ = 0.8 (lagging)
Fuel Consumption (g/kW·h): 225
Max. Output Current (A): 28.8
Phase/Wiring: Three-phase, four-wire
Noise Level (Lp at 7m): 109 dB
Dimensions (mm): 1700 × 700 × 1000
Weight: 650 kg
(2) Diesel Engine:
Brand: Yuchai
Manufacturer: Yuchai Machinery Co., Ltd.
Model: 4D24G4 A
Cooling System: Closed-circuit water cooling
Starting Method: 24V DC electric start
Aspiration: Naturally aspirated
Oil Consumption Rate (g/kW·h): ≤0.8
Number of Cylinders: 4
Total cylinder displacement (L): 2.449
Fuel supply method: Direct injection
Cylinder arrangement: Vertical (in-line)
Intercooling method: Water-cooled intercooler
Fuel type: Domestic No. 0 light diesel
Speed regulation method: Stanadyne mechanical rotary pump
Emission standard: China Stage III
Oil type: WD/40
Bore/Stroke: 87/103 mm
(3) Alternator:
Brand: Marathon Stamford
Origin: Jiangsu
Model: ZD-16-4 (All-copper, brushless)
Material: Pure copper
Insulation class: H
Voltage control method: AVR
Voltage regulation: ≤4%
Rated voltage (V): 400/230
Protection class: IP23
Frequency: 50 Hz
Phase/Wiring: Three-phase four-wire / Y-connection
Frequency regulation rate (%): ≤±0.5 (steady state); +10 to -7 (transient)
Voltage regulation rate (%): ≤±0.5 (steady state); +20 to -15 (transient)
Frequency fluctuation rate (%): ≤±0.5
Voltage fluctuation rate (%): ≤±0.5
II. Configuration
a) Standard configuration
Industrial water-cooled diesel engine
Single-bearing drip-proof alternator, IP22 protection, insulation class H
Radiator for 40°C ambient temperature, dual-layer cooling
Electric start
Standard air filter
Output circuit breaker
Steel base frame with anti-vibration pads
Silencer/Muffler
Battery
Air circuit breaker cabinet (manual)
User operation manual
Notes: 1. The unit adopts an integrated structure; all components are securely mounted on a sturdy channel-steel base.
2. Ensure there are no abnormalities such as oil or water leaks.
3. For direct-injection generator sets, no power derating is required at altitudes below 1,000 meters; between 1,000 and 3,000 meters, derate by 4% for every 500-meter rise; between 3,000 and 5,000 meters, derate by 6% for every 500-meter rise. 4. Actual dimensions and unit weight are subject to the physical product.
III. Optional Accessories (at additional cost):
Battery trickle charger
ATS (Automatic Transfer Switch) panel
Rainproof enclosure/canopy
Soundproof enclosure/canopy
Control panel with self-protection and auto-start functions
Control panel with "Three Remotes" (remote signaling, remote measuring, remote control) functionality
Mobile trailer-mounted power station (enclosure/canopy on trailer)
Soundproof mobile power station (enclosure/canopy on trailer)
Heaters for engine oil, diesel fuel, water jacket, and anti-condensation
Separate daily fuel tank; integrated base fuel tank
No. 120, West Liaoyang Road, Liaoyuan Road Subdistrict, Shibei District, Qingdao City, Shandong Province, China